EasyManua.ls Logo

Honeywell SILENT KNIGHT 6700 - Page 108

Honeywell SILENT KNIGHT 6700
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
108 6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Reporting Receivers Compatible with the Control Panel
EVS Alarm # Point Alarm pi Exp. ID QA (EPPP) E -
Emergency #
PPP - Point #
QANNXXEPPP 1 220 +
Emerge
ncy #
Exp. ID Point #
EVS Alarm # Point Alarm Restore pi Exp. ID QH (EPPP) E -
Emergency #
PPP - Point #
QHNNXXEPPP 3 220 +
Emerge
ncy #
Exp. ID Point #
EVS Alarm # Point Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 242 Exp. ID Point #
EVS Alarm # Point Trouble Restore pi Exp. ID QJ Point # QJNNXXPPPP 3 242 Exp. ID Point #
EVS Alarm # Point Disabled pi Exp. ID QB Point # QBNNXXPPPP 1 243 Exp. ID Point #
EVS Alarm # Point Enabled pi Exp. ID QU Point # QUNNXXPPPP 3 243 Exp. ID Point #
EVS Supervisory/Tamper Alarm pi Exp. ID QS Point # QSNNXXPPPP 1 241 Exp. ID Point #
EVS Supervisory/Tamper Alarm Restore pi Exp. ID QR Point # QRNNXXPPPP 3 241 Exp. ID Point #
EVS Supervisory/Tamper Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 242 Exp. ID Point #
EVS Supervisory/Tamper Trouble
Restore
pi Exp. ID QJ Point # QJNNXXPPPP 3 242 Exp. ID Point #
EVS Supervisory/Tamper Disabled pi Exp. ID QB Point # QBNNXXPPPP 1 243 Exp. ID Point #
EVS Supervisory/Tamper Enabled pi Exp. ID QU Point # QUNNXXPPPP 3 243 Exp. ID Point #
EVS NAC Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
EVS NAC Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
EVS Control Circuit Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
EVS Control Circuit Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
EVS Relay Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
EVS Relay Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
EVS Notification Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
EVS Notification Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
External Reset/Silence/Fire Drill switch
disabled
pi Exp. ID UB Point # UBNNXXPPPP 1 571 Exp. ID Point #
External Reset/Silence/Fire Drill switch
enabled
pi Exp. ID UU Point # UUNNXXPPPP 3 571 Exp. ID Point #
External Reset/Silence/Fire Drill switch
trouble
pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
External Reset/Silence/Fire Drill switch
trouble restore
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
Interlock switch alarm (Water Release Zone) pi Exp. ID FA Point # FANNXXPPPP 1 110 Exp. ID Point #
Interlock switch alarm restore
(Water Release Zone)
pi Exp. ID FH Point # FHNNXXPPPP 3 110 Exp. ID Point #
Interlock switch disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Interlock switch enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Interlock switch trouble (Water Release Zone) pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Interlock switch trouble restore (Water
Release Zone)
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
LOC Mic Activated EVS Alarm pi Exp. ID QA 0 QANNXX0000 1 220 Exp. ID 000
LOC Mic Activated EVS Alarm Restore pi Exp. ID QH 0 QHNNXX0000 3 220 Exp. ID 000
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module ID
# (If Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 10.2 Reporting Formats Table (Continued)

Table of Contents