6700 Manual — P/N LS10148-001SK-E:F 8/29/2022 71
Programming Menu Quick Reference Programming Overview
Point
(cont.)
Internal Power and
External Power
Point #
B SWITCH
6
MANUAL PULL
Latch and Non-Latch feature only
appear for WATERFLOW,FIRE
SUPERVISORY, FIRE TAMPER,
ZONE AUX1, ZONE AUX2,
SYSTEM AUX1, SYSTEM AUX2
Section 8.5.2
WATERFLOW
FIRE SUPER-
VISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX 1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL
RELEASE
INTER-LOCK
STATUS POINT
A SWITCH
6
Same as B SWITCH
B DETECT
6
2-WIRE SMOKE
Zone #
Edit Name
4-WIRE SMOKE
CO 4 WIRE DET
CO 4 WIRE SUP
DET
Latch
Non-Latch
A DETECT
6
2-WIRE SMOKE
4-WIRE SMOKE
CO 4 WIRE DET
CO 4 WIRE SUP
DET
Latch
Non-Latch
5880/5865 Enter Point #
UNUSED
Section 8.5.3
NOTIF
NOTIF OUTPUT
Select Group
Edit Name
CONTROL
CIRCUIT
System
Options
Communication
Options
Auto Time Test
Set the Hour
*02:00AM
Section 8.6.1
Set the Minutes
Select AM/PM
Enter Interval 24 hrs,12 hrs, *6 hrs, 4 hrs
Phone Lines
For each phone line (1 & 2) select:
Dialing Prefix Up to 9 digits *none
# of Answer Rings Range: 00-15 *06
Select Dialing Option
*TT
TT/PL
PULSE
Rotary Pulse Format
*U = 60/40
E = 66/34
Dial Tone Disabled Y or *N
Monitor Line Y or *N
Answering Machine Bypass Y or *N
Phone Line Unused Y or *N
Edit Ethernet
IP Address
Subnet Mask
Default Gateway
DHCP Enable
Menu Options/Defaults Reference
Table 7.4 Programming Quick Reference List (Continued)