EasyManua.ls Logo

Honeywell SILENT KNIGHT 6700 - Page 80

Honeywell SILENT KNIGHT 6700
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
80 6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Programming Point
SK/ SUP
DETECTOR
SUP PHOTO DUCT Latching
Non Latching
Supervisory switches can be latching or non-latching.
SUP SMOKE PHOTO
SUP SMOKE ION
SUP HEAT
SUP ACCLIMATE
SUP HEAT HT
SUP SMOKE
PHOTO/HEAT
SUP SMOKE BEAM
CO SMOKE
DETECTOR
ALRM CO/ALRM
FIRE
SUP CO/ALRM FIRE
ALRM CO/SUP FIRE
SUP CO/SUP FIRE Latching
Non Latching
Detectors programmed as Supervisory can be latching or non-latching.
W-DETECTOR PHOTO Latching
Non Latching
Wireless photoelectric detectors
HEAT Wireless heat detector
PHOTO-HEAT
W-SUP DET Same as
W-Detector
Latching
Non Latching
Wireless photoelectric detectors
SWITCH
MAN_PULL Use this switch type for manual pull stations. This input is always latched. The switch can
clear only when an alarm is reset.
WATERFLOW Latching
Non Latching
Use this switch type for monitoring water flow in a Sprinkler System. Switch closure will
cause a sprinkler alarm. Water flow switches can be programmed as latching or non-
latching.
You can program a delay of up to 90 seconds to be used with a water flow switch. The
delay allows for normal, brief changes in Sprinkler System water pressure. The water flow
alarm will not activate unless the switch is active for the programmed delay time.
Note: Waterflow delay of the FACP and the waterflow device shall not exceed 90 seconds.
If a delay is used, the system begins counting down when the switch closes. If the switch
opens (restores) before the timer expires, a water flow alarm is not generated. If the water
flow switch remains closed after the timer expires, a water flow alarm will be generated.
SUPERVSY Latching
Non Latching
Use this switch type for tamper monitoring of sprinklers and other fire protection devices. If
a contact closes, a sprinkler supervisory event will be generated. Supervisory switches can
be latching or non-latching.
FIRE DRILL System-level, non latching switch. This switch is an alternative way of causing a fire drill. It
has the same operation as the fire drill option available from the annunciator. When the
switch is activated, a fire drill begins; when the switch is de-activated, a fire drill ends.
SILENCE System-level switch provides an alternate way to silence the system; same effect as
pressing the Silence key.
RESET System-level switch provides an alternate way to reset the system; same effect as pressing
the Reset key.
PAS_ACK Positive acknowledge switch. This switch must be used in zones programmed as Positive
Alarm Sequence (see Table 8.2).
If an acknowledge switch closes when an alarm or trouble condition is not already in
progress, a trouble will occur.
You must use a UL listed normally open, momentary switch type. The switch must be rated
at 5V, 100 mA (minimum) and be used with an EOL resistor for supervision.
Type
Selection
Function
Latching
Option
Comments
Table 8.3 Point Programming for Internal SLC Module (Continued)

Table of Contents

Related product manuals