Features 
•  Approved in accordance with EN 54-17 (included in the EN 54-16 approval of the VARIODYN
®
 D1 System) 
•  Up to 4 rings per DOM4-8 or DOM4-24 
•  Up to 500 W power per loop 
•  Up to 5 spurs with more than one loudspeaker per loop (including EOL) 
•  Easy migration of existing spurs into the loop 
•  Fully fail-safe if each loudspeaker is fitted with an LIM  
•  Replaces A/B cabling  
•  Partially eliminates the need for E 30 cabling (DIN VDE 0833-4, chapter 7.10) 
•  Various standard cable types can be used for loudspeakers 
•  Cable leads can be wired in parallel to increase the cable cross-section - Do not route outbound and inbound 
loop conductors in the same cable or the same conduit 
 
Amplifier  Maximum number of LIMs  Max loop length including spur lines 
2XD250  40  1000 
2XD400  64  1000 
4XD250B  25  500 
4XD300  40  1000 
4XD500  50  1000 
 
 
 
•  No other amplifiers are approved for combination with LIMs 
•  Observe the maximum number of LIMs and the loop length for the amplifier used 
•  20 % power reserve per amplifier should be planned in 
•  The maximum load is different for each amplifier and should be determined in consultation with 
the Technical Support. 
 
Three operating modes can be implemented with a DOM4-8 or DOM4-24: 
     
Fig. 14: Operation with  
Fig. 15: Operation with  
Fig. 16: Mixed operation, e.g. with 2 loops