Prerequisite: Remove oil, moisture, and dirt from the intended
mounting surface of the target structure on which the HVSS will be
mounted. If the dirt is strong, remove it with Isopropyl alcohol.
ATTENTION: Use the adhesive mount adapter preferably on a
flat surface. As there is a potential risk of falling down of the
HVSS if it is mounted on uneven, rough, or curved surfaces,
due to lack of sufficient bonding area.
1. Screw-in the adhesive mount adapter into the threaded hole
provided on the base of the HVSS.
2. Firmly hold the base of the HVSS using a spanner (of size 41mm),
and tighten the adapter to the base using another spanner (of
size 32mm).
Ensure a Torque of 3.5 to 4 Nm is applied for tightening.
3. Remove the protective film from adhesive face of the adapter.
4. Stick the HVSS fitted with an adhesive adapter onto the target
structure (like beams, structure, frames, and etc). Apply an
adequate pressure on the HVSS after it is mounted, to ensure
proper bonding of the pressure-sensitive adhesive with the target
structure.