26
Figure 5-2: Adhesive Adapter Mounting
Screw Mounting
Perform the below instruction for screw mounting on the target
structure:
1. Insert the M6 socket head cap screw into the hole provided on the
screw-mount adapter (where the head of the screw sits inside the
adapter and the shank protrudes outwards).
2. Insert the protruding M6 socket head cap screw (with adapter) into
the hole provided on the target structure/bracket, and then secure
the adapter with M6 nut (on the other side of structure/bracket)
using Allen key (of size 5mm) and spanner (of size 10mm). Ensure
a Torque of 16 N-m or 140 in-lbs is applied for tightening.
Or, If there is an existing M6 tapped hole on the target structure,
then you just need to insert the protruding M6 socket head cap
screw (with adapter) into that hole provided on the target
structure/bracket, and tighten with Allen key (of size 5mm).
3. Fit the HVSS onto the secured adapter. Ensure that the orientation
of the HVSS is vertical.
Firmly hold the secured adapter using a spanner (of size 32mm),
and tighten the base of the HVSS to the adapter using another
spanner (of size 41mm). Ensure a Torque of 3.5 to 4 Nm is applied
for tightening.
Chapter 5 - Setting up the Honeywell Versatilis Signal Scout