CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
135 63-4528—04
When start frequency is higher than the min. out put frequency, drives’ output will be from start frequency to the setting
frequency. Please refer to the following diagram for details.
Fcmd=frequency command,
Fstart=start frequency (Pr.01-09),
fstart=actual start frequency of drive,
Fmin=4th output frequency setting (Pr.01-07/Pr.01-41),
Flow=output frequency lower limit (Pr.01-11)
a
01 - 08 Min. Output Voltage of Motor 1
Factory Setting: 0.0/0.0
Settings 230V series 0.0~240.0V
460V series 0.0~480.0V
01 - 09 Start-Up Frequency
Factory Setting: 0.50
Settings 0.0~600.00Hz
fstart F start
FLOW 0
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
M33610
fstart F start
OPERATION AFTER
START-UP
Fstart > Fmin
Fcmd > F min
H Fcmd
H Fcmd
H FLOW
H Fcmd
Fcmd < F min
Fcmd > F min
Fcmd > FLOW
FLOW 0
BY
PR.01-34
BY
PR.01-34
BY
PR.01-34
Fcmd
Hz
TIME
Fmin
Fstart
Fcmd
Hz
TIME
Fmin
Fstart
Fcmd 1
H FLOW
FLOW > Fcmd1
> Fmin
Fcmd 2
Hz
60Hz
TIME
BY PR.01-34
Fmin > F cmd2
Fmin
FLOW
Fcmd 1
H Fcmd 1
Fcmd 1 > FLOW
&
Fcmd 1 > Fmin
Fcmd 2
BY PR.01-34
Fcmd 2 > FLOW &
Fcmd 2 < Fmin
Fmin
FLOW
Hz
60Hz
TIME