12
Output/Relay Devices
• 4204 and 4204CF Relay Modules, and 4101SN V-Plex Relay Modules can be used to program up to 96 outputs.
Outputs can be activated in response to system events (alarm condition), at a specific time of day, at random
times, and manually using the #70 Relay Command Mode.
a. One additional style-Y supervised Notification Appliance Circuit using a 4204CF.
Other Devices
• The ADEMCO 4146 Keyswitch on any one of the system's eight partitions.
• A Commercial Fire Listed 24VDC Power Supply may be used to power 24V notification appliances.
Arming/Disarming and Bypassing
• Can arm the system with zones faulted (Vent Zone). These zones are automatically bypassed and can be
programmed to automatically unbypass when the zone restores.
• Can arm with entry/exit and interior type zones faulted (Arm w/Fault). These zones must be restored before the
exit delay expires, otherwise an alarm is generated.
L/
• Vent zones cannot be used in UL installations.
• You must disable the Force Arm option (used in conjunction with the Arm w/Fault option), in UL and ULC
installations.
• Provides global arming capability (ability to arm all partitions the user code has access to in one command).
• Provides the ability to exit an armed premises temporarily without having to disarm and then rearm the system
(Quick Exit).
Quick Exit is not permitted for use in a UL commercial installation.
• Can be armed in one of three STAY modes or Instant modes, automatically bypassing specific burglary zones
regardless of the zone response type.
• Can automatically bypass specific zones if no one exits the premises after arming (Auto-STAY). Auto-STAY will
not occur if the system is armed via an RF transmitter, scheduling, access control, keyswitch or downloading.
• Can bypass a group of zones with one set of keystrokes.
• Supports Exit Error Logic, whereby the system can tell the difference between a regular alarm and an alarm
caused by leaving an entry/exit door open. If the system is not subsequently disarmed, faulted entry/exit zone(s)
and/or interior zones are bypassed and the system arms.
• Supports Recent Close report, which is designed to notify the central station that an alarm has occurred within
2 minutes after the exit delay has expired.
Partitioning
• Can control 8 separate areas (partitions) independently, each functioning as if it had its own separate control.
All fire zones must be assigned to partition 1.
• Provides a Common Lobby partition, which can be programmed to arm automatically when the last partition is
armed, and to disarm when the first partition is disarmed.
• Provides a Master partition (9), used for the purpose of viewing the status of all partitions at the same time.
• Can display fire, burglary, panic, and trouble conditions at all other partitions’ keypads (selectable option).
Scheduling
• Can automate system functions, such as arming, disarming, and activation of outputs (e.g., lights).
• Provides access schedules (for limiting system access to users by time).
• Provides an End User Output Programming Mode, allowing the user to control outputs.
U
LC
Scheduling is currently not approved for ULC applications.
Access Control
• Supports 15 VistaKey modules single-door access control modules
• Supports up to 500 access cards (250 for the VISTA-128FBPT).
• Can store access control events in the event log.