Walk Testing the ‘Smart’ V-Plex Motion Detectors
Normally, in the test mode, the LED on the ‘Smart’ V-Plex Motion Detectors like the DT7500SN and IS2500SN is
disabled. In order to have the LED illuminate during the test mode, the PIR zone number must be entered into the
system’s test memory. To do this, once in the Walk Test Mode enter [3-digit zone number] + [#].
To remove a zone from the system’s test memory, enter [3-digit zone number] + [
].
NOTES:
1 beep indicates a correct zone number entry.
2 beeps indicate an incorrect entry.
The system’s test memory capacity is 5 zones.
When the test mode is exited the system’s test memory is cleared.
Armed Burglary System Test
Alarm messages are sent to the central station during the armed tests. Notify the central station that a test will
be in progress.
A display of “COMM FAILURE” indicates a failure to communicate (no kissoff by the receiver at the central
station). If this occurs, verify that the phone line is connected, the correct report format is programmed, etc.
To perform an armed burglary test, proceed as follows:
Step Action
1
Notify the central station that a test of the system is being performed.
2
Arm the system.
3
Fault one or more zones.
4
Silence alarm sounder(s) each time by entering the code and pressing OFF.
NOTE: The system must be rearmed after each code + off sequence.
5
Check that entry/exit delay zones provide the assigned delay times.
6
Check the keypad-initiated alarms, if programmed, by pressing the panic key pairs (
and #, 1 and
, and/or 3
and #).
The word ALARM and a descriptor “999” are displayed for
and #. If [1] and [
] are pressed, “995” is
displayed; if [3] and [#] are pressed, “996” is displayed.
7
If the system has been programmed for audible emergency, the keypad emits a loud, steady alarm sound.
Silence the alarm by entering the security code and pressing OFF. If the system has been programmed for
silent panic, there are no audible alarms or displays. A report is sent to the central station, however.
8
Notify the central station that all tests are finished, and verify results with them.
Testing Wireless Transmitters
Transmitter ID Sniffer Mode
Use the Transmitter Sniffer Mode to test that transmitters have all been properly programmed.
If a transmitter does not have its serial number “enrolled,” it will not turn off its zone number.
To enter the Transmitter ID Sniffer Mode, proceed as follows:
Step
Action
1
Enter Installer Code + [#] + [3]. The keypad displays all zone numbers of wireless units programmed into
the system.
2
Fault each wireless zone, causing each device to transmit.
As the system receives a signal from each of the transmitters, the zone number of that transmitter
disappears from the display.
3
Enter
Installer Code + OFF
to exit the Sniffer Mode.