EasyManua.ls Logo

Honeywell VISTA-128FBPT - Using the 3 STAY key

Honeywell VISTA-128FBPT
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
Wiring 2-Wire Smoke Detectors to Zones 1 and 2
2K EOL resistors must be used on fire zones and must be connected across the loop wires of each zone at the
last detector.
To wire 2-wire smoke detectors to zone 1 and/or zone 2, perform the following steps:
Step
Action
1
Select 2-wire smoke detectors from the list of compatible detectors.
2
Connect 2-wire smoke detectors across zone 1 (terminals 15 and 16), and/or zone 2 (terminals 17 and 18) as
shown in Figure 3-10. Observe proper polarity when connecting the detectors.
3
Connect the EOL resistor at the last detector in the loop across the zone 1 terminals. The EOL resistor
must be connected across the loop wires at the last detector.
Figure 3-10: 2-Wire Smoke Detector on Zone 1 (for zone 2 use terminals 17 and 18)
Using 4-Wire Smoke Detectors on Zones 1-8
U
LC
For ULC fire installations, 4
-
Wire Smoke Detectors must not be connected to the fire transmitter. These devices
must be connected to the Fire Alarm Control Panel.
You may use as many 4-wire smoke detectors as can be powered from the panel's Auxiliary Power output without
exceeding the output's rating (1A (for Canada 650mA)).
Auxiliary power to 4-wire smoke detectors is not automatically reset after an alarm, and therefore must be
momentarily interrupted using the auxiliary relay.
Compatible 4-Wire Smoke Detectors
Use any UL Listed 4-wire smoke detector that is rated for 12VDC operation and that has alarm reset time not exceeding
6 seconds. Some compatible 4-wire smoke detectors are listed below.
DETECTOR TYPE MANUFACTURER MODEL #
4-Wire Photoelectric Smoke Detector DSC FSA-410B
4-Wire Photoelectric Smoke Detector w/Heat Detector DSC FSA-410BT
4-Wire Photoelectric Smoke Detector w/Sounder & Heat Detector DSC FSA-410BST
4-Wire Photoelectric Smoke Detector w/Aux. Relay & Heat Detector DSC FSA-410BRT
4-Wire Photoelectric Smoke w/Aux. Relay, Sounder & Heat Detector DSC FSA-410BRST
End of Line Power Supervision Relay for FSA-410 Series Smoke Detectors DSC RM-2
Polarity reversal module for FSA-410 series Smoke Detectors DSC PRM-4WC
4-Wire Photoelectric Smoke Detector System Sensor 4W-B
4-Wire Photoelectric Smoke Detector w/Heat Detector System Sensor 4WT-B
4-Wire Photoelectric Smoke Detector w/Sounder & Heat Detector System Sensor 4WTA-B
4-Wire Photoelectric Smoke Detector w/Aux. Relay & Heat Detector System Sensor 4WTR-B
4-Wire Photoelectric Smoke Detector w/Aux. Relay, Sounder & Heat Detector System Sensor 4WTAR-B
4-Wire Photoelectric Smoke Detector w/Aux. Relay, Sounder & Isolated Heat Detector System Sensor 4WITAR-B
4-Wire Photoelectric Air Duct Smoke Detector, Extended Air Speed Range System Sensor DH100ACDCLP
4-Wire Ionization Air Duct Smoke Detector System Sensor DH100ACDCI

Table of Contents

Other manuals for Honeywell VISTA-128FBPT

Related product manuals