10
Program feature or option
Permitted in
Settings permitted in UL 864
3ā
50 ZONE TYPES 16-18 REST.
N
1 = enable
M ust be set t o ā1ā (en abl e).
3ā
55 RESET ON 2
ND
OFF FOR
BELL 1
N 0 = disable
1 = enable
M ust be set t o ā0ā (di sabl e).
3ā
56 RESET ON 2
ND
OFF FOR
BELL 2
N 0 = disable
1 = enable
M ust be set t o ā0ā (di sabl e).
3ā
57 CONFI RM ARM BELL 2,
AUX
N 0 = disable
1 = enable
Must be set to ā0, 0ā (disable).
3ā
59 CHIME ON BELL 2, AUX
N 0 = disable
M ust be set t o ā0ā (di sabl e) i f Bel l 2
or A ux Rel ay i s used for F i r e.
3ā
60 BELL 2, AUX RLY
Y
En t er 01-15 multiplied by 2 minutes.
00 = no t i m eou t .
M ust be set t o ā3ā (M i ni mu m of 6
minutes).
3ā
82 BURG FEATURES
N
1 = enable
M ust be set t o ā0ā (di sabl e).
RESTRI CTI ON FOR FI RE
RELAYS
Y
No
Rest r i ct i on f or # 70 mu st be set t o
Yes wh en pr ogr am mi n g fi r e r el ays.
Programming Field Settings for ULC304 Compliance
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES
SECTION 1
This product incorporates field-programmable software. In order for the product to comply with the requirements
in the Standard for Signal Receiving Centre and Premise Burglar Alarm Control Units, ULC S304, certain
programming features or options must be limited to specific values or not used at all as indicated below.
Program feature or option Possible settings Settings permitted in ULC S304
38 PREVENT ZONE XXX
BYPASS (PARTITION
SPECIFIC)
En t er a zone num ber (001-250).
Enter 000 if al l zones can be
bypassed.
Must be set to ā000ā (all zones can be bypassed).
1ā
58 EN ABLE 5800 RF FORCE
ARM
0 = disable
1 = enable
M ust be set t o ā0ā (di sabl e).
2ā
03 UL C S304 ENABL E
0 = disable
1 = enable
M ust be set t o ā1ā (en abl ed).
2ā
08 FORCE-ARM ENABLE
(PARTITION SPECIFIC)
0 = disable
1 = enable
M ust be set t o ā0ā (di sabl e).