UL864 (Commercial Fire) Compliance
⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠⢠ā¢
General Requirements
The VISTA-128FBPT/VISTA250FBPT control panels provide features that allow the system to meet UL864 Commercial
Fire requirements. To meet these requirements, follow the guidelines outlined in this section.
⢠The reporting of bypassed points to the central station must be enabled in Report Code Programming mode.
⢠Fire alarm notification circuits must be supervised (e.g., supervisory zones 970 and 971 for Bell 1 and Bell 2
outputs)
⢠Only one relay of the 4204CF can be programmed for a NAC. If the 4204CF relay is programmed as a NAC, the
stop action must be programmed as a zone type 62, Bell 2 Timeout.
⢠Output devices are not intended for overriding automatic fire and building functions.
⢠Line cut detection must be enabled for both the main and backup phone lines (supervisory zones 974 and 975).
⢠Access Control Devices cannot be used.
⢠Audio Alarm Verification Devices cannot be used.
⢠Remote downloading can only be performed if a service person is at the premises.
⢠All supervision zones for the polling loop, RF receivers, keypads, NAC outputs, and telephone lines that are used,
must be enabled as zone type 19 (24-hour trouble).
Programming Field Settings for UL864 Compliance
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements
in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features
or options must be limited to specific values or not used at all as indicated below.
Program feature or option Permitted in
UL864? Y/N
Possible settings Settings permitted in UL 864
ā
08 TEMPORAL SIREN PUL SE
N
1 = enable
N ot u sed at t h i s t i m e. M u st be set t o
ā0ā (disable).
ā
13 BELL 1 TI M EOUT
Y En t er 01-15 m
00 = no t i m eou t .
M ust be set t o ā3ā (Minimum of 6
minutes).
ā
14 RS232 comm.
N
M ust be set t o ā 0ā.
ā
17 AC LOSS KEYPAD
N
1 = enable
M ust be set t o ā1ā (en abl ed).
ā
19 RANDOMIZE AC LOSS
REPORT
Y 0 = within 2 minutes
1 = 10-40 minut es
2 = 1-3 hou r s
3 = 6-12 hours wit hout Type 13, 1-3
hours with Type 13
M ust be set t o ā2ā.
ā
20 TELEPHONE MODULE
PH ONE CODE
N
1-9 = fi r st digi t of access code
or # = second di gi t of access code
(en t er # +11 for ā āā, or # +12 for ā#ā)
T o di sabl e ent er 00 f or t h e 1
st
digit
N ot U sed. M u st be set t o ā00ā .
ā
22 KEYPAD PANIC ENABLES
N
1 = enable
Must be set to ā000ā for par t it ion 1
i n fi r e syst ems.
ā
23 MULTIPLE ALARMS
(PARTITION SPECIFIC)
N 0 = disable
M ust be set t o ā1ā (en abl ed).
ā
24 IGNORE EXPANSION
ZONE TAMPER
N 0 = disable (tamper detection)
1 = enable (no t amper det ect i on )
M ust be set t o ā0ā (en abl ed).
ā
26 INTELLIGENT TEST
N
1 = enable
M ust be set t o ā0ā (di sabl e).