8
Program feature or option
Permitted in
UL864? Y/N
Possible settings
Settings permitted in UL 864
āˆ—
27 TEST REPORT INTERVAL
Y
Enter 0001-9999 f or t he t est r epor t
interval in hours.
Enter 0000 for t est r epor t i ng.
Must be set to ā€œ0024ā€ (M aximum 24
hour s)
āˆ—
28 POWER-UP I N PREV. STATE
Y
0 = disable
1 = enable
M ust be set t o ā€œ1ā€ (en abl e).
āˆ—
37 DOWNLOAD COMM AN D
ENABLES
N
0 = disable
1 = enable
M ust be set t o ā€œ0ā€ for al l ent r i es
(disable).
āˆ—
41 N ORM AL L Y CL OSED OR
EOLR (ZONES 3-8)
N
0 = E OL R su per vi si on
1 = N.C. loops
M ust be set t o ā€œ0ā€ (E OL R
Super vi si on ).
āˆ—
42 DIAL TONE PAUSE
Y
En t er t he w ai t t i m e for di al t one
det ect i on :
0 = 5 seconds; 1 = 11 seconds; 2 = 30
seconds.
M ust be set t o ā€œ0ā€ (5 seconds).
āˆ—
44 RI NG DETECTION COUNT
N
En t er 00 t o di sable r i ng det ect i on.
En t er 01-14 for ring counts of 1-14.
En t er 15 t o sel ect An swer i ng
M achi ne Def eat M ode
Must be set to ā€œ00ā€ (disable).
āˆ—
56 DYNAMIC SIGNAL DELAY
Y
En t er 00-15 t imes 15 seconds.
M ust be set t o ā€œ6ā€ (90 seconds).
āˆ—
77 AUTO TRBL RSTR
Y
0 = disable
1 = enable
M ust be set t o ā€œ1ā€ (en abl e).
āˆ—
80 ZONE TYPE 9 -10, 14
RESTORE
N
0 = disable
1 = enable
M ust be set t o ā€œ1ā€ (en abl e) for zone
t ype 9.
āˆ—
84 SWI N GER SUPPRESS.
(PARTITION – SPECI FI C)
N
En t er 01-14,
En t er 00 for u nl i m i t ed r epor t s
Must be set to ā€œ00ā€ (disable).
1āˆ—
12 PROGRAM N OTI FI CATI ON
Y
0 = no
1 = yes
M ust be set t o ā€œ1ā€ (yes).
1āˆ—
13 SYS. SENSOR REV. RELAY
N 0=use nei t her Zone 1 or Zone 2
inputs
1=use Zone 1 i nput ;
2=use Zone 2 i nput ;
3=use Zone 1 and Zone 2 inputs.
N ot U sed. M u st be set t o ā€œ0ā€ .
1āˆ—
18 AFFECTS LOBBY
(PARTITION – SPECI FI C)
N
0 = disable
1 = enable
M ust be set t o ā€œ0ā€ (di sabl ed) for
par t it ion 1.
1āˆ—
19 ARMS LOBBY (PARTITION
– SPECI FIC)
N
0 = disable
1 = enable
M ust be set t o ā€œ0ā€ (di sabl ed) for
par t it ion 1.
1āˆ—
22 thru
1āˆ—
25 CROSS-ZONI N G
PAI RS (1 – 4)
N
Enter 001-250
Enter 000,000 to disable
Must be set to ā€œ000,000ā€ (disabled)
for fi r e zon es.
1āˆ—
28 RF TX LOW BATTERY
SOU N D
N
0 = di sar med st at e on l y
1 = bot h ar med and di sar med st at es
Must be set t o ā€œ1ā€ (bot h ar med an d
di sar med st at es).
1āˆ—
29 RF TX LOW BATTERY
REPORTI NG
N
0 = disable
1 = enable
M ust be set t o ā€œ1ā€ (en abl e).
1āˆ—
30 RF RCVR CH ECK -IN
INTERVAL
N
En t er 02–15 t imes 2 hour s (4–30
hour s)
En t er 00 t o di sable r ecei ver
super visi on
Maxi mum is 02 (4 hour s) for fir e
installations.
1āˆ—
31 RF TX CH ECK -IN
INTERVAL
N
En t er 02–15 t imes 2 hour s (4–30
hour s)
Enter 00 to di sable tr ansmit t er
super visi on
Maxi mum is 02 (4 hours) for fi re
installations.
1āˆ—
35 ACS DLR ENABLES
N 0 = disable
1 = enable
N ot u sed. M ust be set t o ā€œ 0ā€.
1āˆ—
44 RF KEYPAD TAMPER
DETECTION
N 0 = disable
1 = enable
N ot u sed. M ust be set t o ā€œ 0ā€.
1āˆ—
45 EXIT DELAY SOUNDING
(PARTITION SPECIFIC)
N
0 = disable
1 = enable
M ust be set t o ā€œ0ā€ (di sabl e) for
par t it ion 1.
1āˆ—
48 RF KEYPAD ASSI GN 1-
8=PART. 0=NO
N 0 = none
1-8 = par t i t i on num ber
N ot u sed. M ust be set t o ā€œ 0ā€.