83
Appendix B: Specifications
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
VISTA-128FBPT/VISTA-250FBPT CONTROL
Physical: 18"H X 14-1/2"W X 4.3"D
Electrical:
Primary Power: From ADEMCO No. 1451 Transformer with enclosure; rated 18VAC, 72VA.
Backup Battery: 12VDC, 12AH min to 34.4AH max. lead acid battery (gel type).
Alarm Power: 12VDC, 1.7A max. for each Notification Appliance Circuit.
Aux. Standby Pwr 12VDC, 1A (For Canada 650mA) max.
Total Power Combined auxiliary standby and alarm currents must not exceed 2.3A (For Canada
1.95A).
Standby Time: 24 hours with 1A (For Canada 650mA) aux standby load using 34.4AH battery.
Fusing: Battery input, auxiliary and Notification Appliance Circuits are protected using PTC
circuit protectors. All outputs are power limited.
Main Dialer
Line Seize: Double Pole
Ringer Equivalence: 0.7B
FCC Registration No.: AC3-USA-68192-AL-E
TLM Threshold Good line when tip-to-ring voltage greater than approximately 25V (13 when blue
jumper cut) or when handset current greater than approximately 10mA. Bad line
when both voltage and current below these levels.
Formats: ADEMCO Contact ID; ADEMCO 10-Digit Contact ID and 4+2 Express
Compatible Receivers
7810iR-en t
MX8000
5140DLM BACKUP DIALER MODULE
Physical: 2.75”H X 4”W X 1”D
Mounts on VISTA-128FBPT main PC board shield using standoffs supplied.
Connects to VISTA-128FBPT main PC board J3 header using ribbon cable supplied.
FCC Registration: AC3-USA-62628-MO-N
UL/ULC Listings:
Control Units and Accessories for Fire Alarm Systems
Equipment for Fire Signal Receiving Centers and Systems
Proprietary Burglar Alarm Units and Systems
Central Station Burglar-Alarm Units
Signal Receiving Centre and Premise Burglar Alarm Control Units
Digital Alarm Communicator System Units
Police Station Connected Burglar Alarm Units and Systems
Local Burglar Alarm Units and Systems
Household Fire Warning System Units
Household Burglar-Alarm System Units
Residential Fire Warning System Control Units
Preliminary Standard for Household Burglar Alarm System Units
Standard for Local Burglar Alarm Units and Systems