83
Appendix B: Specifications
VISTA-128FBPT/VISTA-250FBPT CONTROL
Physical: 18"H X 14-1/2"W X 4.3"D
Electrical:
Primary Power: From ADEMCO No. 1451 Transformer with enclosure; rated 18VAC, 72VA.
Backup Battery: 12VDC, 12AH min to 34.4AH max. lead acid battery (gel type).
Alarm Power: 12VDC, 1.7A max. for each Notification Appliance Circuit.
Aux. Standby Pwr 12VDC, 1A (For Canada 650mA) max.
Total Power Combined auxiliary standby and alarm currents must not exceed 2.3A (For Canada
1.95A).
Standby Time: 24 hours with 1A (For Canada 650mA) aux standby load using 34.4AH battery.
Fusing: Battery input, auxiliary and Notification Appliance Circuits are protected using PTC
circuit protectors. All outputs are power limited.
Main Dialer
Line Seize: Double Pole
Ringer Equivalence: 0.7B
FCC Registration No.: AC3-USA-68192-AL-E
TLM Threshold Good line when tip-to-ring voltage greater than approximately 25V (13 when blue
jumper cut) or when handset current greater than approximately 10mA. Bad line
when both voltage and current below these levels.
Formats: ADEMCO Contact ID; ADEMCO 10-Digit Contact ID and 4+2 Express
Compatible Receivers
7810iR-en t
MX8000
5140DLM BACKUP DIALER MODULE
Physical: 2.75”H X 4”W X 1”D
Mounts on VISTA-128FBPT main PC board shield using standoffs supplied.
Connects to VISTA-128FBPT main PC board J3 header using ribbon cable supplied.
FCC Registration: AC3-USA-62628-MO-N
UL/ULC Listings:
Standard. No.
Name
Edition
UL864
Control Units and Accessories for Fire Alarm Systems
Ninth
ULC-S559-04
Equipment for Fire Signal Receiving Centers and Systems
First
UL1076
Proprietary Burglar Alarm Units and Systems
Fifth
UL1610
Central Station Burglar-Alarm Units
Third
CAN/ULC-S304-06
Signal Receiving Centre and Premise Burglar Alarm Control Units
Second
UL1635
Digital Alarm Communicator System Units
Third
UL365
Police Station Connected Burglar Alarm Units and Systems
Fourth
UL609
Local Burglar Alarm Units and Systems
Eleventh
UL985
Household Fire Warning System Units
Fifth
UL1023
Household Burglar-Alarm System Units
Sixth
ULC-S545-02
Residential Fire Warning System Control Units
Second
ULC/ORD-C1023-74
Preliminary Standard for Household Burglar Alarm System Units
First
ULC-S303-M91
Standard for Local Burglar Alarm Units and Systems
First