SPYDER MODEL 7 VAV CONTROLLER  INSTALLATION INSTRUCTIONS
31-00475-01   24
BACNET MSTP WIRING
The MSTP variants of the Spyder Model 7 VAV controller 
use the BACnet MSTP communication protocol. The 
controller’s data is presented to other controllers over a 
twisted-pair MSTP network, using the TIA/EIA 485 
signaling standard capable of the following baud rates: 
9.6, 19.2, 38.4, 57.6, and 76.8 kb/s. The Spyder Model 7 
BACnet MSTP controllers are server devices on the 
MSTP network. Each Spyder Model 7 BACnet controller 
uses a high-quality TIA/EIA 485 transceiver and exerts 
1/8 unit load on the MSTP network. 
According to U.L. requirements, each RS-485 interface 
may be loaded with a maximum of 32 unit loads. 
Depending on the actual performance and connection 
speed, connecting fewer BACnet MSTP devices per 
network is recommended. It is recommended to have 
less than 40 controllers on a single MSTP network.
The controller features a 2-wire non-isolated RS-485 
interface (terminals 32, 33, and 34) suitable for BACnet 
MSTP communication. The terminal block containing it 
is gray. The cable length affects the baud rate. See 
Table 18.
NOTE:
The maximum length of a BACnet MSTP network 
bus segment with recommended wiring is 4,000 ft 
(1200 m). Repeaters must be used when making 
runs longer than 4,000 ft (1200 m). Between any 
two devices, a maximum of three repeaters can be 
used.
Termination Resistors
Matched terminating resistors are required at each end 
of a segment bus wired across (+) and (-). Use matched 
precision resistors rated ¼ W ±1 % / 80 = 130 Ω. 
Ideally, the value of the terminating resistors should 
match the rated characteristic impedance of the 
installed cable. For example, if the installed MSTP cable 
has a listed characteristic impedance of 120 Ω, install a 
120 Ω resistor.
RS-485 Bias Switches
Each RS-485 port has an adjacent 3-position biasing 
switch, with these settings:
• BIA - (Default, middle) Controller provides RS-485 
biasing, but without a termination resistor.
• END - Both RS-485 biasing and a termination 
resistor are provided by the controller.
• MID - No RS-485 biasing or termination resistor is 
provided by the controller.
Often, adding RS-485 biasing can improve 
communications by eliminating indeterminate idle 
states.
BACnet MSTP Wiring Example
Following proper MSTP cabling shield grounding 
procedures is important to minimize the risk of 
communication problems and equipment damage 
caused by capacitive coupling. Capacitive coupling is 
caused by placing MSTP cabling close to lines carrying 
higher voltage. The shield should be grounded on only 
one end of the MSTP segment, for example, on the earth 
ground terminal on the WEB-8000 and to earth ground.
Fig. 28  BACnet MSTP Wiring Example with WEB-8000 or CIPer Model 50
Table 18  Baud Rate vs Maximum Cable Length
Baud Rate
Maximum Cable 
Length (L)
9.6, 19.2, 38.4, 57.6, and 76.8 kbps
4000 ft (1200 m)