Specifications 87
This equipment must be located in the same immediate area (such as adjacent cabinets) as any
other equipment that has a connection between the earthed conductor of the same DC supply
circuit and the earthing conductor, and also the point of earthing of the DC system. The DC
system must be earthed elsewhere.
The DC supply source is to be located within the same premises as the equipment.
Switching or disconnecting devices must not be in the earthed circuit conductor between the
DC source and the point of connection of the earthing electrode conductor.
WARNING: To reduce the risk of electric shock, energy hazards, fire, and damage to the
equipment, you must install this product in accordance with the following guidelines:
This equipment must be installed by trained service personnel, as defined by the NEC and IEC
60950-1, Second Edition, the standard for Safety of Information Technology Equipment.
This power supply is intended only for installation in HP servers located in a restricted access
location.
In accordance with applicable national requirements for Information Technology Equipment
and Telecommunications Equipment, this power supply only connects to DC power sources
that are classified as SELV or TNV. Generally, these requirements are based on the
International Standard for Information Technology Equipment, IEC 60950-1. In accordance
with local and regional electric codes and regulations, the DC source must have one pole
(Neutral/Return) reliably connected to earth ground.
This power supply is not intended for direct connection to the DC supply branch circuit.
Connect this power supply to a power distribution unit (PDU) that provides an independent
overcurrent-protected output for each DC power supply.
The branch circuit overcurrent protection must be rated 24 A.
You must connect the power supply ground screw located on the front of the power supply to
a suitable ground (earth) terminal. In accordance with local and regional electric codes and
regulations, this terminal must be connected to a suitable building ground (earth) terminal. Do
not rely on the rack or cabinet chassis to provide adequate ground (earth) continuity.

Table of Contents

Other manuals for HP ProLiant DL320e Gen8 v2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP ProLiant DL320e Gen8 v2 and is the answer not in the manual?

HP ProLiant DL320e Gen8 v2 Specifications

General IconGeneral
ProcessorIntel Xeon E3-1200 v3 series
Processor Sockets1
MemoryUp to 32GB
Memory Slots4
Form Factor1U Rack
Memory TypeDDR3 UDIMM
StorageUp to 4 LFF or 8 SFF drives
RAID SupportHP Dynamic Smart Array B120i
Expansion Slots1 PCIe 3.0
ManagementHP iLO