Troubleshooting  53 
Off  On  Off 
On—
Battery 
capacity 
<25% 
On—
Battery 
capacity 
>25% 
On—
Battery 
capacity 
>50% 
On—
Battery 
capacity 
>75% 
Off 
UPS is on battery (on page 
55)—No utility power 
*  *  *  Off  *  *  Flashing  * 
Overtemperature condition 
(on page 56) 
Off  Off  On  Flashing  Flashing  Flashing  Flashing  Flashing 
Internal UPS fault condition 
(on page 56) 
Flashin
g 
Off  Off  Flashing  Flashing  Flashing  Flashing  Flashing 
REPO condition (on page 
56) 
*  Off  *  Off  *  Flashing  *  * 
Site wiring condition (on 
page 56) 
*  Off  *  On  On  On  On  Flashing 
Overload condition (on page 
57)—UPS power capacity is 
exceeded with no other faults 
*  Off  *  Off  *  *  *  Flashing 
Overload condition (on page 
57)—UPS power capacity is 
exceeded while other faults 
exist 
Off  On  Off 
On—
Battery 
capacity 
<25% 
On—
Battery 
capacity 
>25% 
On—
Battery 
capacity 
>50% 
On—
Battery 
capacity 
>75% 
Flashing 
Overload condition (on page 
57)—UPS power capacity is 
exceeded while on battery 
with no other faults 
Off  On  Off  Off  Off  Off  Flashing  Flashing 
Overload condition (on page 
57)—UPS power capacity is 
exceeded while on battery 
with overtemperature fault 
Off 
Flashin
g 
Off  Flashing  Flashing  Flashing  Flashing  Flashing  Unit is powering down 
Flashin
g 
Flashin
g 
Flashin
g 
Flashing  Flashing  Flashing  Flashing  Flashing 
Checksum failure error (on 
page 57) 
 
* This LED can be in any state. 
For the location of individual LEDs, see "UPS front panel LED indicators (on page 8)." 
 
UPS is in Auto-Bypass mode 
The UPS transfers from Operate mode (on page 38) to Auto-Bypass when one of the following fault 
conditions is detected: 
•  Inverter AC over voltage 
•  Inverter AC under voltage 
•  Rectifier input over current 
•  Inverter output over current 
•  Inverter fault 
•  Heat sink over temperature 
•  Fan failure