Component identification 9
The front panel is shown with the bezel removed.
Item LED description Load level
1 Self Test OnThe load level is greater than 10%.
2 Battery Fault OnThe load level is greater than 25%.
3 Site Wiring Fault OnThe load level is greater than 50%.
4 Overtemperature OnThe load level is greater than 75%.
5 Overload OnThe load level is greater than 100%.
6 On Bypass
7 On Battery
8 Utility
For more information, see "LED troubleshooting (on page 52)" .
HP UPS R/T3000 models
UPS model Description
R/T3000 NA and R/T3000j
JPN
Domestic/Japanese
Low-voltage
Nondetachable NEMA L5-30 plug
R/T3000h NA and R/T3000h
JPN
Domestic
High-voltage
Nondetachable NEMA L6-20 plug
R/T3000 INT
International
High-voltage
Detachable country-specific plug
R/T3000 NA and R/T3000j JPN rear panel

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R3000 and is the answer not in the manual?

HP R3000 Specifications

General IconGeneral
ModelR3000
Capacity3000 VA / 2700 W
Rack Size2U
Frequency50/60 Hz
Output Voltage230V
Input Voltage230V
Battery TypeSealed Lead Acid (SLA)
InterfaceSerial, USB
Output ConnectionsIEC 320 C13, IEC 320 C19
Transfer Time4 ms
Efficiency95%
Operating Temperature0°C to 40°C
Storage Temperature-15°C to 45°C
Humidity5% to 95% non-condensing
Dimensions432 x 88 x 650 mm