Troubleshooting 57
Overload condition
All the load LEDs are illuminated.
Action:
1. Power down the UPS ("Powering down the UPS" on page 42).
2. Remove one or more load devices to reduce the power requirements.
3. Wait at least 5 seconds and restart the UPS.
4. If the condition persists, verify that the load devices are not defective.
Checksum failure error
A Checksum failure error occurs when executing a bad load sequence, or having an incorrect EEPROM
map while loading software through the serial or USB port.
Action:
1. Rerun the firmware upgrade.
2. If the condition persists, contact an HP authorized service representative.
UPS does not start
Action:
1. Be sure that the power cord is plugged in to a utility power receptacle.
2. Check the power source at the utility power receptacle.
Low battery shutdowns
Ungraceful shutdown of attached servers occurs when the UPS is in a low battery condition.
Action:
1. Verify that the power management software is not delaying the shutdown of attached servers when
the UPS is in a low battery condition.
2. Allow the UPS batteries to charge for 24 hours.
3. If the Battery Fault LED is red, replace the batteries ("UPS battery replacement procedure" on page
46).
UPS does not provide the expected backup time
Action:
1. If the Overload LED ("UPS front panel controls" on page 8) is illuminated, remove one or more load
devices to reduce the power requirements.
2. Power down the UPS ("Powering down the UPS" on page 42).
3. Allow the UPS batteries to charge for 24 hours.
4. Initiate a self-test ("Initiating a self-test" on page 41).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R3000 and is the answer not in the manual?

HP R3000 Specifications

General IconGeneral
ModelR3000
Capacity3000 VA / 2700 W
Rack Size2U
Frequency50/60 Hz
Output Voltage230V
Input Voltage230V
Battery TypeSealed Lead Acid (SLA)
InterfaceSerial, USB
Output ConnectionsIEC 320 C13, IEC 320 C19
Transfer Time4 ms
Efficiency95%
Operating Temperature0°C to 40°C
Storage Temperature-15°C to 45°C
Humidity5% to 95% non-condensing
Dimensions432 x 88 x 650 mm

Related product manuals