4. With one person on each side, lift the chassis to rail level and slide the chassis on the mounting rails.
5. Attach the chassis to the rack using the supplied screws.
Connecting the ERM to the UPS
Connect both ends of the split ERM cable to the ERM connectors on the UPS rear panel. To install additional
ERMs, connect both ends of the split ERM cable from the next ERM into the connectors on the rear panel of
the previous ERM. Up to four ERM units can be connected.
Charging the ERM batteries
Connect the UPS to a grounded utility power outlet. When the UPS is plugged in, it automatically enters
Standby mode and begins charging the ERM batteries. With the UPS in Standby mode, allow the ERM
batteries to charge before putting the UPS into service.
IMPORTANT: When the ERM is initially installed, the batteries may not be fully charged. Hewlett
Packard Enterprise recommends that the batteries charge for at least 24 hours before supplying backup
power to devices to ensure that full battery runtime is available.
IMPORTANT: To verify the attached ERMs are recognized, confirm the number of installed ERMs using
the UPS front panel control through the UPS Status Menu.
24 Installation

Table of Contents

Other manuals for HPE G2 R6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE G2 R6000 and is the answer not in the manual?

HPE G2 R6000 Specifications

General IconGeneral
Form FactorRack-mountable
Battery TypeSealed Lead-Acid (SLA)
Nominal Output Voltage230 V
Frequency50/60 Hz
Input Voltage200 V AC to 240 V AC
Output Voltage200 V AC to 240 V AC
InterfaceUSB
Capacity6000 VA
Battery RuntimeVaries based on load (typically 5-15 minutes at full load)

Related product manuals