Action
1. Verify that all batteries are properly connected.
2. If condition persists, contact your service representative.
Battery fault
Symptom
LED is on, continuous beep.
Cause
The battery test failed due to bad or disconnected batteries.
The battery minimum voltage is reached and the UPS is in ABM cycling mode.
Action
1. Verify that all batteries are properly connected.
2. Start a new battery test.
If condition persists, contact your service representative.
Backup time
Symptom
The UPS does not provide the expected backup time.
Cause
The batteries need charging or service.
Action
1. Apply utility power for 48 hours to charge the batteries.
2. If condition persists, contact your service representative.
Bypass mode
Symptom
LED is on.
Cause
An overload or a fault has occurred.
A command has been received and the UPS is in Bypass mode.
32 Troubleshooting

Table of Contents

Other manuals for HPE G2 R6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE G2 R6000 and is the answer not in the manual?

HPE G2 R6000 Specifications

General IconGeneral
Form FactorRack-mountable
Battery TypeSealed Lead-Acid (SLA)
Nominal Output Voltage230 V
Frequency50/60 Hz
Input Voltage200 V AC to 240 V AC
Output Voltage200 V AC to 240 V AC
InterfaceUSB
Capacity6000 VA
Battery RuntimeVaries based on load (typically 5-15 minutes at full load)

Related product manuals