Action
1. Equipment is powered but not protected by the UPS.
2. Check one of the following alarms.
Overtemperature
Overload
UPS failure
Power overload
Symptom
LED is on, beep is continuous.
Cause
Power requirements exceed the UPS capacity.
Action
1. Remove some of the equipment from the UPS
2. The UPS continues to operate, but may switch to Bypass mode or shut down if the load increases.
3. The alarm resets when the condition becomes inactive.
UPS overtemperature
Symptom
LED is on, one beep every three seconds.
Cause
The UPS internal temperature is too high or a fan has failed. At the warning level, the UPS generates the
alarm but remains in the current operating state. If the temperature rises another 10ºC (50ºF), the UPS
transfers to Bypass mode or shuts down if Bypass is unusable.
Action
1. If the UPS transferred to Bypass mode, the UPS will return to normal operation when the temperature
drops to 5ºC (41ºF) below the warning level.
If the condition persists, shut down the UPS.
2. Clear vents and remove any heat sources. Allow the UPS to cool. Ensure the airflow around the UPS is
not restricted.
3. Restart the UPS.
4. If the condition continues to persist, contact your service representative.
Troubleshooting 33

Table of Contents

Other manuals for HPE G2 R6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE G2 R6000 and is the answer not in the manual?

HPE G2 R6000 Specifications

General IconGeneral
Form FactorRack-mountable
Battery TypeSealed Lead-Acid (SLA)
Nominal Output Voltage230 V
Frequency50/60 Hz
Input Voltage200 V AC to 240 V AC
Output Voltage200 V AC to 240 V AC
InterfaceUSB
Capacity6000 VA
Battery RuntimeVaries based on load (typically 5-15 minutes at full load)

Related product manuals