Troubleshooting resourcesTroubleshooting resources
Troubleshooting resources are available for HPE Gen11 server products in the following documents:
Troubleshooting Guide for HPE ProLiant Gen11 servers provides procedures for resolving common problems and comprehensive
courses of action for fault isolation and identification, issue resolution, and software maintenance.
Error Message Guide for HPE ProLiant Gen11 servers and HPE Synergy provides a list of error messages and information to assist with
interpreting and resolving error messages.
Integrated Management Log Messages and Troubleshooting Guide for HPE ProLiant Gen11 servers and HPE Synergy provides IML
messages and associated troubleshooting information to resolve critical and cautionary IML events.
To access troubleshooting resources for your product, see the Hewlett Packard Enterprise websiteHewlett Packard Enterprise website .
SpecificationsSpecifications
SubtopicsSubtopics
Environmental specificationsEnvironmental specifications
Mechanical specificationsMechanical specifications
Power supply specificationsPower supply specifications
Hot-plug power supply calculationsHot-plug power supply calculations
Environmental specificationsEnvironmental specifications
SpecificationSpecification ValueValue
Temperature rangeTemperature range —
Operating 10°C to 35 °C (50°F to 95°F)
Nonoperating -30°C to 60 °C (-22°F to 140°F)
Relative humidity (noncondensing)Relative humidity (noncondensing) —
Operating Minimum to be the higher (more moisture) of -12°C (10.4°F) dew point or 8% relative humidity
Maximum to be 24°C (75.2°F) dew point or 90% relative humidity
Nonoperating 5% to 95%
38.7°C (101.7°F), maximum wet bulb temperature
All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 304.8 m (1.8°F per 1000 ft) to 3048 m (10,000 ft) is
applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). The upper limit and rate of change
might be limited by the type and number of options installed.
For certain approved hardware configurations, the supported system inlet temperature range is extended:
5°C to 10°C (41°F to 50°F) and 35°C to 40°C (95°F to 104°F) at sea level with an altitude derating of 1.0°C per every 175 m (1.8°F per
every 574 ft) above 900 m (2953 ft) to a maximum of 3048 m (10,000 ft).
40°C to 45°C (104°F to 113°F) at sea level with an altitude derating of 1.0°C per every 125 m (1.8°F per every 410 ft) above 900 m