EASYTEST-COMBI519
EN - 49
5.
If the instrument detects that the phase L and neutral N
leads are inverted, it does not carry out the test and a
screen similar to the one reported to the side is
displayed. Rotate the mains plug or check the
connection of measuring cables.
RCD 15/10 18:04
TT
T
Ut
=
=
- - -
- - -
ms
V
FREQ. = 50.00Hz
VL-PE= 1V
VL-N=231V
Exchange L-N
X1
30mA
MODE
In
Type
Ut
6.
If the instrument detects that the phase and PE leads
are inverted, it does not carry out the test and a screen
similar to the one reported to the side is displayed.
Check the connection of measuring cables.
RCD 15/10 18:04
TT
T
Ut
=
=
- - -
- - -
ms
V
FREQ. = 50.00Hz
VL-PE=231V
VL-N=1V
Exchange L-PE
X1
30mA
MODE
In
Type
Ut
7.
If the instrument detects the absence of the signal to
terminal B3 (PE conductor), it provides the warning
screen shown to the side and blocks the execution of
the tests.
RCD 15/10 18:04
TT
T
Ut
=
=
- - -
- - -
ms
V
FREQ. = 50.00 Hz
VL-PE= 114V
VL-N=231V
Missing PE
X1
30mA
MODE
In
Type
Ut
8.
If the instrument detects the absence of the signal to
terminal B4 (neutral conductor), it provides the warning
screen shown to the side and blocks the execution of
the tests.
RCD 15/10 18:04
TT
T
Ut
=
=
- - -
- - -
ms
V
FREQ. = 50.00 Hz
VL-PE= 231V
VL-N=115V
Missing N
X1
30mA
MODE
In
Type
Ut