55
Function 11 DHW Priority
Description: Allows the user to set DHW priority time, which is the amount of time to shut down the
hydronic heating module when the system control senses a large domestic hot water usage. Factory
default 30
minutes (Range 0 to 60
minutes).
Function 12 Error Outdoor Sensor
Description: Allows the user to set the control to display an error message if an outdoor sensor is open or
shorted. NOTE: This error does not stop the appliance from running. Factory default ON
(Selection
ON/OFF/PHOEN ON).
Function 13 Error System Sensor
Description: Allows the user to set the control to display an error message if the system sensor is open or
shorted. NOTE: This error does not stop the appliance from running. Factory default ON
(Selection
ON/OFF).
NOTE: Press ENTER to store system parameters.
Function 14 Service Schedule
Description: Allows the user to program the heater maintenance schedule by selecting a service date or
time based on the heater run hours. Factory default OFF (Selection - Date or Run Hours). NOTE: Without
setting this function, Functions 33 through 36 will not display.
Function 15
Year
Description: This parameter sets the year of the next service reminder.
Hours
Description: This parameter sets the 2 left digits of the amount of run hours until the next service
reminder. If you selected the run hour function, you will need to program 10,000 hours.
Function 16
Description: If you selected the date function, you will need to program the month.