FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
B Technical Specifications (Dual–Live Wire 208 V
Power System)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
B Technical Specifications (Dual–Live
Wire 208 V Power System)
Table B-1 Key technical specifications
≤ 2 (including the Converged Cabinet and
network cabinet)
208 V/2 Ph/60 Hz input, 120 V/1 Ph/60 Hz
output
Maximum power of a single cabinet
≤ 1000 m, derated within the altitude range
of 1000 m to 4000 m
Installed on a concrete floor or raised floor
Routed in from the top and bottom
If the battery is installed in another
equipment room, temperature of the
smart module equipment room should be
in the range of 0°C to 40°C.
If the battery is installed in the same
equipment room as the smart module,
the room temperature should be in the
range of 18°C to 27°C.