3.3 Cooling System
The cooling system is deployed by customers by default. Civil air conditioners can be
configured to cool equipment based on the equipment room temperature.
If the battery is installed in another equipment room, temperature of the smart module equipment
room should be in the range of 0°C to 40°C.
If the battery is installed in the same equipment room as the smart module, the room temperature
should be in the range of 18°C to 27°C.
3.4 Management System
3.4.1 Overview
The smart module monitoring solution consists of the collector and monitoring components.
The ECC800e functions as the collector.
The smart module provides a module-level pad for local intelligent management in terms of
real-time monitoring, status browsing, alarm management, and system configuration.
The NetEco can manage the infrastructures of a single data center or of data centers in various
areas in a centralized manner. The BIN4.0/SNMP protocol used for the northbound interface
is opened, so that the third-party NMS can be connected.
The ECC800e manages the real-time status, alarms, and configuration information about the
devices inside the smart module. It also provides a graphical user interface (GUI) for ease of
operating and maintaining devices inside the smart module.
The ECC800e manages the real-time status, alarms, and configuration information about the
devices inside the smart module. It also provides a graphical user interface (GUI) for ease of
operating and maintaining devices inside the smart module.
3.4.2 ECC800e
The ECC800e monitors the equipment and environment inside the smart module.
The ECC800e supports alarm notification by SMS and email, enabling remote maintenance. Information
about a maximum of 20 users who will receive alarm notification can be displayed.