FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
3 Alarm Reference
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
61
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
Alarm
Name
Sever
ity
System Action
Cause
Solution
on
addition, the
discharger
cannot be
started. If the
mains is
abnormal, the
system will
transfer to
bypass mode or
shut down
based on logic.
threshold.
The
configured
number of
batteries is
less than the
actual number.
The actual
number of
batteries does
not meet
requirements.
batteries
matches the
actual number.
3. Check that the
actual number of
batteries meets
requirements.
0036
-2
Battery
mainte
nance
remind
er
Warni
ng
None.
The time for
maintenance
arrives.
Maintain the
batteries.
0037
-1
Battery
underv
oltage
Critic
al
The system exits
from battery mode
and transfers to a
working mode
based on logic.
The UPS
works long in
battery mode.
The charger is
faulty.
1. Check whether
the battery
voltage is
normal.
2. Check whether
the output is
overloaded.
3. Check whether
any battery is
damaged. If yes,
replace the
battery.
4. Check whether
any battery
charger
generates an
alarm. If yes,
replace the
faulty module.
0040
-7
Rectifi
er
abnorm
al
Critic
al
1. The system
shuts down the
module.
2. If only one
module is
working, or the
The fan for the
power module
is abnormal.
The air
channel of the
power module
1. Check that the
air channel for
the module is
free from
blockage.
2. Check whether