FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
3 Alarm Reference
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
65
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
Alarm
Name
Sever
ity
System Action
Cause
Solution
ass
bypass mode.
transfers to bypass
mode.
0088
-1
Rack
address
conflict
Critic
al
None.
The configured
rack address
conflicts with
another one.
Check the rack
address setting.
0089
-1
Rack
output
overloa
d
Minor
This alarm does not
trigger any action.
The load is
excessive.
The rack
capacity
setting is not
appropriate.
1. Check the load.
Remove some
loads or expand
the UPS power
capacity if the
UPS is
overloaded.
2. Check that the
configured rack
capacity meets
requirements.
0090
-1
Dry
contact
board
fault
Critic
al
This alarm does not
trigger any action.
The dry contact
board MUE05A
I2C
communication
fails.
Replace the dry
contact board
MUE05A.
0090
-2
The dry contact
board MUE06A
I2C
communication
fails.
Replace the dry
contact board
MUE06A.
0356
Battery
mode.
Minor
None.
Battery mode.
Running status
displayed. See
details about how to
handle other alarms.
0359
No
power
supplie
d
Warni
ng
None.
No power
supplied
Running status
displayed. See
details about how to
handle other alarms.
0332
Output
disable
d
Minor
None.
Output disabled
Running status
displayed. See
details about how to
handle other alarms.