FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
3 Alarm Reference
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
66
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
Alarm
Name
Sever
ity
System Action
Cause
Solution
0337
PDC
bypass
input
breaker
open
Critic
al
None.
The bypass input
circuit breaker on
the PDC is OFF.
Running status
displayed. No
suggested measures.
0338
The
output
circuit
breaker
on the
PDC is
OFF.
Critic
al
None.
The output circuit
breaker on the
PDC is OFF.
1. Check that all
UPS output
switches are ON.
2. On the LCD,
check that PDC
output breaker
open alarm has
disappeared. If
the alarm
persists, tap the
Clear Fault
button to clear
the alarm.
0341
The
mainte
nance
circuit
breaker
on the
PDC is
ON.
Minor
None.
The maintenance
circuit breaker on
the PDC is ON.
Running status
displayed. No
suggested measures.
0342
The
mains
input
circuit
breaker
is OFF.
Critic
al
None.
The mains input
circuit breaker is
OFF.
Running status
displayed. No
suggested measures.
0343
BPM
input
breaker
open
Critic
al
None.
BPM input
breaker open
Running status
displayed. No
suggested measures.
0340
Maint.
breaker
closed
Minor
None.
Maint. breaker
closed
Running status
displayed. No
suggested measures.
0345
The
Critic
None.
The battery
Running status

Table of Contents