FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
3 Alarm Reference
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
67
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
Alarm
Name
Sever
ity
System Action
Cause
Solution
battery
circuit
breaker
is OFF.
al
circuit breaker is
OFF.
displayed. See
details about how to
handle other alarms.
0335
Genera
tor
connec
ted
Warni
ng
None.
Generator
connected
Running status
displayed. No
suggested measures.
0594
-1
Insuffi
cient
redund
ant
racks
Minor
This alarm does not
trigger any action.
The load is
excessive.
The
configured
number of
redundant
racks is
incorrect.
1. Reduce the load.
2. Decrease the
configured
number of
redundant racks.
0095
-1
Insuffi.
redund
ancy
Minor
This alarm does not
trigger any action.
The load is
excessive.
The
configured
number of
redundant
modules is
incorrect.
1. Reduce the load.
2. Decrease the
configured
number of
redundant
modules.
0096
-1
ECO
volt.
abnorm
al
Minor
1. The system
cannot transfer
to ECO bypass
mode.
2. If the system
works in ECO
bypass mode, it
transfers to
inverter or
bypass mode or
stops output.
The ECO
bypass voltage
or frequency is
out of the
preset range.
The ECO
bypass voltage
or frequency
range is
incorrectly set.
The bypass
input sequence
is reverse or
the neutral
wire is
disconnected.
1. Check the
bypass input
voltage and
frequency.
2. Check that the
rated voltage,
rated frequency,
ECO bypass
voltage range,
and frequency
range are
correctly set.
3. Check that the
bypass power
cable or circuit
breaker is
connected.