Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
Alarm
Name
Sever
ity
System Action
Cause
Solution
eck
ng
self-check.
is complete.
0148
ATS
fault
Minor
None.
ATS
communicatio
ns parameters
are modified.
ATS cables
are
disconnected.
The ATS is
faulty.
Restore the ATS
communications
parameters to
default values.
Check the
communications
cable
connections.
Check the ATS.
0103
Input
SPD
alarm
Minor
None.
The input SPD is
faulty.
Check the input
SPD.
0349
Cabine
t input
breaker
open
Minor
None.
The mains input
circuit breaker is
OFF.
Turn on the mains
input circuit
breaker.
0193
Mains
three-p
hase
current
imbala
nce
Warni
ng
None.
The load power
among three
phases is
unbalanced.
Check the load.
0009
Mains
overloa
d
Minor
None.
Phase L1, L2, or
L3 is overloaded.
Check phase A
loads.
0196
Branch
overloa
d
Critic
al
None.
A branch is
overloaded.
Check the branch
loads.
0197
Mains
overcur
rent
Minor
None.
Phase L1, L2, or
L3 experienced
overcurrent.
Check phase L1,
L2, or L3 loads.
0198
Branch
Current
High
Minor
None.
A branch
experienced
overcurrent.
Check the branch
loads.
0199
Mains
underc
Warni
ng
None.
Phase L1, L2, or
L3 experienced
Check phase L1,
L2, or L3 loads.