FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
3 Alarm Reference
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
70
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
Alarm
Name
Sever
ity
System Action
Cause
Solution
urrent
overcurrent.
0200
Branch
underc
urrent
Warni
ng
None.
A branch
experienced
overcurrent.
Check the branch
loads.
0370
Branch
switch
open
Critic
al
None.
A branch switch
is OFF.
Check the status of
the branch switch.
0203
Branch
switch
abnorm
al
Warni
ng
None.
A branch is not
connected to
loads.
Check the branch
loads.
0211
ATS
non-aut
o mode
Minor
None.
The ATS
switchover mode
is set to manual
mode.
Set the ATS
switchover mode to
automatic mode.
0212
Main
temper
ature
abnorm
al
Critic
al
None.
Overload for a
long time
Unreliable
copper bar
connection
Check that there
is no overload.
Power off the
UPS and check
whether the
copper bar is
reliably
connected.
0213
Branch
temper
ature
abnorm
al
Critic
al
None.
Overload for a
long time
Unreliable
copper bar
connection
Fire
Check whether
there is a branch
fire.
Check that there
is no overload.
Power off the
UPS and check
whether the
copper bar is
reliably
connected.
0216
ATS
backup
power
abnorm
Critic
al
None.
One ATS power
supply is
abnormal.
Check whether two
ATS power inputs
are normal.