SUN2000 (8KTL-28KTL)
User Manual
Copyright © Huawei Technologies Co., Ltd.
5.4.2 Connecting RS485 Communications Cables
Connect the SUN2000 to communications equipment (such as the data collector and PC)
using RS485 communications cables.
Context
A 24 AWG outdoor shielded network cable with the following specifications is recommended
for use as an RS485 communications cable:
With an internal resistance less than or equal to 1.5 ohms/10 m
With an outer diameter of 4.5-7.5 mm (8 core wires, each with a diameter of 1.00-1.07
mm)
A waterproof RJ45 connector has five parts: shielded plug, plastic housing, coupling nut, seal
ring, and sealing nut. See Figure 5-27.
Figure 5-27 Waterproof RJ45 connector composition
When routing communications cables, ensure that they are separated from power cables and
away from interference sources to prevent communication interruptions.
Procedure
Step 1 Remove an appropriate length of the insulation layer from the shielded network cable using a
wire stripper.
A 24 AWG outdoor shielded network cable with the following specifications is recommended
for use as an RS485 communications cable:
With an internal resistance less than or equal to 1.5 ohms/10 m