Figure 7-7 Feature parameters (special user)
----End
Parameter List
Parameter
Description Remarks
Automatic OFF due
to communication
interrupted
The standards of certain countries and
regions require that the inverter must
shut down after the communication is
interrupted for a certain time.
If Automatic OFF due to
communication interrupted is
set to Enable and the inverter
communication is interrupted for
a specied time (set by
Communication interruption
duration), the inverter will
automatically shut down.
Automatic ON due
to communication
resumed
If this parameter is set to Enable, the
inverter automatically starts after
communication recovers. If this
parameter is set to Disable, the
inverter needs to be started manually
after communication recovers.
This parameter is displayed when
Automatic OFF due to
communication interrupted is
set to Enable.
Communication
interruption
duration (min)
Species the duration for determining
communication interruption. Used for
automatic shutdown for protection in
case of communication interruption.
N/A
Soft start/boot time
(s)
Species the duration for the power to
gradually increase when the inverter
starts.
N/A
SUN2000-(50KTL, 60KTL, 65KTL)-M0
User Manual 7 Man-Machine Interactions
Issue 11 (2024-02-02) Copyright © Huawei Technologies Co., Ltd. 96