Parameter Description Remarks
String detection
reference
asymmetric
coecient
Species the threshold for
determining PV string exception. The
false alarms caused by xed shadow
shading can be controlled by
changing this parameter.
This parameter is displayed when
String monitor is set to Enable.
String detection
starting power
percentage (%)
Species the threshold for starting PV
string exception detection. The false
alarms caused by xed shadow
shading can be controlled by
changing this parameter.
Tracker controller Selects a controller vendor. N/A
Duration for
determining short-
time grid
disconnection (ms)
The standards of certain countries
and regions require that the
SUN2000 should not disconnect from
the power grid if the power grid
experiences a short-time failure. The
SUN2000 output power should be
recovered immediately after the fault
is rectied.
N/A
7.2.2 Operations Related to the Special User
If you log in to the app as Special User, you can set grid parameters, protection
parameters, feature parameters, and power adjustment parameters for the
SUN2000.
7.2.2.1 Setting Grid Parameters
Procedure
Step 1 Choose Function Menu > Settings > Grid Parameters to access the settings
screen.
SUN2000-(50KTL, 60KTL, 65KTL)-M0
User Manual 7 Man-Machine Interactions
Issue 11 (2024-02-02) Copyright © Huawei Technologies Co., Ltd. 91