Figure 7-39 Performing quick setting using a saved file 
 
 
 
 
To change the configuration file to be imported, tap Change. 
 
In the dialog box with Are you sure you want to configure the inverter connected router settings 
again, if you tap Confirm, the previously saved router configurations will be cleared. If you tap 
Cancel, you only have to enter the saved router password. 
 
After quick setting is complete, tap Switch to Router WiFi to switch to the Available WiFi 
networks nearby screen and tap the corresponding router WiFi connection to switch to the router 
WiFi network. 
 
To connect to the router WiFi network from the mobile phone system after router parameters are 
successfully set, you need to log out of the app and log in again. 
 
After the management system is successfully connected, the SUN2000 will report the SN and 
installer registration code. If the connection fails, another connection attempt will start after 10 
seconds. The installer registration code is generated by the SUN2000 automatically and is used for 
the installer to register with the management system and manage the inverter. 
----End 
7.4.5 Setting Grid-Connection Parameters 
Setting Grid-Connection Parameters 
To set grid codes, choose Grid-connect config from the Operation console screen. 
 
Before setting a grid code, ensure that the DC side of the inverter is energized. Voltage level, Grid 
frequency, and Output mode do not have to be set because they are associated with the grid code.