In UPS setting mode, hold down the ON/MUTE button for more than 3s to go to the
previous option after a beep sound; hold down the SELECT button for more than 3s to go to
the next option after a beep sound; and hold down the OFF/ENTER button for more than 3s
to
conrm the setting.
Procedure
1. Power on the UPS. The UPS enters standby mode, as shown in Figure 5-1.
Hold down the SELECT button for 5s to enter UPS setting mode.
Figure 5-1 Default screen after UPS power-on
2. Set the output voltage based on the actual value. The voltage can be set to
200 V, 208 V, 220 V, 230 V (default), or 240 V.
Figure 5-2 Setting the voltage level
3. Set the output frequency based on the actual value. The frequency can be set
to 50 Hz, 60 Hz, or AUT (automatic, default).
Figure 5-3 Setting the voltage frequency
4. (Only for the UPS with long backup time) Set the battery capacity based on
the actual total capacity of all battery strings. The default value for the UPS
UPSJZ-T-(1 kVA–3 kVA)
User Manual 5 Operations
2022-08-15 78