3.4 Fieldbus Type Address Map
99
(2) Input and Output Signal Assignment for each Axis
The I/O signals for each axis consists of 4 words for each I/O bit register.
The control signals and status signals are ON/OFF signals in units of bit.
For the current position, 2-word (32-bit) binary data is available and values from -999999 to
+999999 (unit: 0.01mm) can be used. Negative numbers are to be dealt with two’s
complement.
For the indicated position number and complete position number, 1-word (16-bit) binary data
is available and values from 0 to 255 can be used.
PLC Output (m is PLC output top word address for each axis number)
Address m
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Unavailable
Address m+1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Unavailable
Address m+2
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Specified
Position No.
PC128
PC64
PC32
PC16
PC8
PC4
PC2
PC1
Address m+3
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Control Signal
BKRL
MODE
PWRT
JOG+
JOG-
JVEL
JISL
SON
RES
STP
HOME
CSTR
Caution : Set the operational condition in advance with using a teaching tool such as PC
software in the position number to be used. Selecting a position number with no
setting conducted will generate the alarm code 0A2 “Position Data Error”.
1 word=16 bit
ME0306-2A