2. ACON, PCON
38
2.6.5  Full Direct Value Mode (Number of Occupied Bytes: 32) 
This is the operation mode with all the values (target position, speed, etc.) set up directly using values from 
PLC. Set each value in the I/O area.
The robot cylinder's effective main functions that can be controlled using this mode, are as shown in the 
following table. 
ROBO cylinder function 
{: Direct control 
x: Disable 
Home-return operation 
{
Positioning operation 
{
Speed and acceleration / deceleration 
setting 
{
Pitch feed (inching) 
{
Pressing operation 
{
Speed change during the movement 
{
Operation at different acceleration and 
deceleration 
{
Pause
{
Zone signal output 
{
PIO pattern selection  x 
(1)  PLC address configuration (* "n" indicates the first address of each axis.) 
Parameter 
No.84
ACON/PCON input register
PLC output 
address (bytes)
ACON/PCON output register 
PLC input 
address (bytes)
n, n+1  n, n+1 
Target position 
n+2, n+3 
Current position 
n+2, n+3 
n+4, n+5  n+4, n+5 
Positioning band 
n+6, n+7 
Command current 
n+6, n+7 
n+8, n+9  n+8, n+9 
Speed
n+10, n+11 
Current speed 
n+10, n+11 
n+12, n+13  Alarm code  n+12, n+13 
Zone boundary + 
n+14, n+15 
n+14, n+15 
n+16, n+17  n+16, n+17 
Zone boundary - 
n+18, n+19 
n+18, n+19 
Acceleration n+20, n+21  n+20, n+21 
Deceleration n+22, n+23  n+22, n+23 
Pressing current-limiting 
value
n+24, n+25 
n+24, n+25 
ACON Occupied area 
PCON
Load current 
threshold 
n+26, n+27 
n+26, n+27 
Control signal 1  n+28, n+29 
Occupied area 
n+28, n+29 
3
Control signal 2  n+30, n+31  Status signal  n+30, n+31 
(Note)  The areas denoted by Occupied area cannot be used for any other purpose. 
Also, exercise caution to avoid node address duplication.