I Single Package Heat Pumps Installation Instructions
6. Raise corner of unit top at least 2" (50.8mm). Place a
sturdy brace at least 2" (50.8mm) thick between cor-
ner and unit top. A 2X4 piece of wood is ideal for this.
7. Disconnect all wires from blower housing and slide
blower housing out of unit.
8. When finished, reassemble in reverse order.
FIGURE 17
Blower Access Showing
Lid Propped with 2X4
Blower Wire Color Identification
Circulating Air Blower
Visually inspect the blower wheel for accumulations of dirt
or lint. Clean the compartment and the blower wheel. If ac-
cumulation is excessive on blower wheel, or does not easi-
ly remove, it will be necessary to remove the blower
assembly.
CAUTION
Do NOT use 3 in 1 oil, penetrating oil, WD40 or similar
oils to oil motor bearings.
Oil the blower motor by adding 1/2 teaspoonful (1cc) of SAE
10W30 to each motor bearing. The blower motor should be
oiled after five years of operation and every five years
thereafter.
Use FIGURE 18 on page 23 to identify wires on blower mo-
tor.
Tochange speed tap settings, see Speed Taps in the Start-
up Procedures section of this manual.
FIGURE 18 _ Wire Colors