70
auxiliary input #2 / hold aux relay on any motion / hold aux relay
on arming loop assertion”
Auxiliary output #2 pulse duration “0.1 seconds to 5.0 seconds”
Auxiliary output #3 function “output disabled / secondary
entrapment alarm / hold aux relay when maintenance due / hold
aux relay on auto-close delay / unlock pulse / pulse aux relay on
close limit switch / pulse aux relay on open limit switch / pulse aux
relay on open motion / pulse aux relay on close motion / hold aux
relay on close limit switch / hold aux relay on open limit switch /
hold aux relay on opening motion / hold aux relay on closing
motion / pulse aux relay on motion prewarn / pulse aux relay on
opening prewarn only / pulse aux relay on closing prewarn only /
pulse aux relay on auxiliary input #1 / hold aux relay on auxiliary
input #1 / pulse aux relay on auxiliary input #2 / hold aux relay on
auxiliary input #2 / hold aux relay on any motion / hold aux relay
on arming loop assertion”
Auxiliary output #3 pulse duration “0.1 seconds to 5.0 seconds”
o Loop and Remote Assignment
Loop functionality assignment, J3 slot “loop slot disabled / safety
loop / free exit loop / shadow loop / arming loop”
Loop functionality assignment, J5 slot “loop slot disabled / safety
loop / free exit loop / shadow loop / arming loop”
Loop functionality assignment, J7 slot “loop slot disabled / safety
loop / free exit loop / shadow loop / arming loop”
Remote control button assignment “remote not used / open-only
command / single command”
o Physical Gate Setup
Number of gate leafs installed “1 / 2” 1 is single gate, 2 is master
slave
Motor type (must be AC hydraulic pump) “DC geared / DC direct
drive / AC hydraulic pump”
Position feed back sensor installed (for model HYJG only factory
set Enabled) “Disabled / Enabled”
Right-Hand of Left-Hand selection “right-hand / left-hand” This
selects which gate starts first in a master slave system.
Leaf stagger delay “0.0 seconds to 15.0 seconds”
Service
o Service Lockout
Set service lockout for all maintenance “controller enabled /
controller disable (gate will not move)”
o Maintenance reminders
Service reminder maintenance not required / Maintenance required
Reset service cycle counter to zero “no / yes”
Set service reminder on cycle counter “off / xxx (factory set at
2500”
Set service reminder on or after date “Disabled / Enabled”