106
INFOSEC UPS SYSTEM 15, Rue du Moulin 44880 Sautron France www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 fax : +33(0)2 40 94 29 51 hotline@infosec.fr 02 19 AA 59 203 07
Charging Voltage
--
Set battery charging voltage. (2.30~2.35V)
2.35V (Default)
Set battery float voltage. (2.23~2.35V)
2.29V (Default)
Auto-Restart
Battery Voltage
--
Set auto-restart battery voltage. (0 or 12.0V~13.0V)
0V (Default)
Pre-Alarm Screen
The Pre-Alarm Setup Screen and Setting options are shown below. Pre-Alarm Setting can be access in any
operation mode.
Pre-Alarm Setup Screen
Setup-Pre-Alarm Setting List
Setting Item
Sub Item
Explanation
Line Voltage
Range
--
Set line voltage range:
Upper limit
+5%
+10%
+15%
+20% (Default)
Lower limit
-5%
-10%
-15%
-20% (Default)
Line
Frequency
Range
--
Set line frequency range:
Upper / Lower limit
+/- 1Hz
+/- 2Hz
+/- 3Hz
+/- 4Hz (Default)
Load
--
Set UPS overload percentage (40~100%)
100% (Default)
Set UPS load unbalance percentage (20~100%)
100% (Default)
3-2-5. Parallel Setup Screen
Simply touch on the “PARALLEL” tab to show parallel function page as shown below.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INFOSEC UPS SYSTEM E4 Evolution II TT Series and is the answer not in the manual?

INFOSEC UPS SYSTEM E4 Evolution II TT Series Specifications

General IconGeneral
BrandINFOSEC UPS SYSTEM
ModelE4 Evolution II TT Series
CategoryUPS
LanguageEnglish

Related product manuals