Charging Voltage
--
Set battery charging voltage. (2.30~2.35V)
2.35V (Default)
Set battery float voltage. (2.23~2.35V)
2.29V (Default)
Auto-Restart
Battery Voltage
--
Set auto-restart battery voltage. (0 or 12.0V~13.0V)
0V (Default)
Pre-Alarm Screen
The Pre-Alarm Setup Screen and Setting options are shown below. Pre-Alarm Setting can be access in any
operation mode.
Pre-Alarm Setup Screen
Setup-Pre-Alarm Setting List
Setting Item
Sub Item
Explanation
Line Voltage
Range
--
Set line voltage range:
Upper limit
+5%
+10%
+15%
+20% (Default)
Lower limit
-5%
-10%
-15%
-20% (Default)
Line
Frequency
Range
--
Set line frequency range:
Upper / Lower limit
+/- 1Hz
+/- 2Hz
+/- 3Hz
+/- 4Hz (Default)
Load
--
Set UPS overload percentage (40~100%)
100% (Default)
Set UPS load unbalance percentage (20~100%)
100% (Default)
3-2-5. Parallel Setup Screen
Simply touch on the “PARALLEL” tab to show parallel function page as shown below.