Contact service personnel.
Synchronized trigger signal fault
Contact service personnel.
Contact service personnel.
Line SCR short circuit fault
Contact service personnel.
Contact service personnel.
Fault! Parallel Cable
Loosen Fault
Check if the parallel cable is loose
and contact service personnel.
Fault! DSP MCU Stop
Communicate
Contact service personnel.
Fault! Bypass
Temperature Fault
Check if the ambient temperature
is over specification.
Or contact service personnel.
Contact service personnel.
Check if the connector is loose
when EPO acts abnormally.
The load devices are demanding more
power than the UPS can supply. Line
mode will transfer to Bypass mode.
Reduce some load and check
output Load-Capacity and
specification
Warning! Communicate
CAN Fail
Contact service personnel.
In Line mode, the load devices are
demanding more power than the UPS
can supply.
Reduce some load and check
output Load-Capacity and
specification
Battery is not connected.
5. Check battery breaker.
6. Check if the battery
connection is well connected.
7. Check the setting of Nominal
Battery voltage.
8. Contact service personnel if
necessary.
Warning! Battery voltage
High
Battery voltage is too High
Check the setting of Nominal
Battery voltage and contact
service personnel.
Warning! Turn On
Abnormal
Check if the input voltage or
frequency is out of range.
Contact service personnel.
Contact service personnel.
Check if the fan is blocked or
contact service personnel.
Warning! Line Phase Error
Check if the Mains phase
sequence is correct and contact
service personnel.
Warning! Bypass Phase
Error
Check if the Bypass phase
sequence is correct and contact
service personnel.
Check if the Neutral connection is
well and contact service
personnel.
Warning! Internal Initial
Fail
Contact service personnel.