Warning! Comm. Syn.
Signal Fail
Communicate Synchronization Signal
Fail
Contact service personnel.
Warning! Comm. TRIG0
Fail
Communicate Trigger signal fault
Contact service personnel.
Warning! Power Stage
Loss
As stated.
Check if the number of power
stage/module installed in the
system is correct.
Warning! Parallel Sys
Config. Wrong
Parallel System Configure error
Contact service personnel.
Warning! Maintenance
Bypass
Enter maintenance
Check if the connector is loose
when it acts abnormally.
Warning! Battery Age Alert
Battery Life expiration
Check if the battery has been
used over its service age. Or
contact service personnel.
Warning! Parallel UPS
Cable Loosen
As stated.
Check if the Parallel UPS Cable is
loose and contact service
personnel.
Warning! Parallel UPS
Config. Wrong
Parallel UPS Configure error
Check the Parallel UPS Setting is
correct and contact service
personnel.
Warning! Parallel
Firmware Error
Power Stage parallel firmware error
The firmware version does not
support UPS Parallel feature.
Contact service personnel.
Warning! ID Conflict
Power Stage ID conflict.
There are two Power
Stages/Modules with the same ID
numbers. Change the repeated ID
to release it. Or contact service
personnel.