Revision 4.02 June. 2000 3
Installing your Model 3000 / Access 4000 system.
Control Module Parts List
- Control Module PCB mounted on metal chassis in metal box.
- Tamper switch bracket.
- Telephone line cable. (Note: Non-standard configuration. Only suitable for use with this product)
- Installation Kit containing:
- 9 x plastic “D” bungs. Must be fitted to all unused cable entry cutouts in the cover.
- 1 x Special AC Powercord entry “D” bung.
- 6 x 8 Way plug-on screw terminals.
- 8 x 2 Way plug-on screw terminals.
- Tamper switch.
- Tamper switch bracket.
- Telecom Line cord.
- 2 x 6.3mm Tamper switch connectors.
- 2 x 4.8mm Battery terminal connectors.
- 1 x 2 Amp M205 (20mm) Fuse. (Spare)
- 20 x 2k2 End-of-line resistors. 16 x Zone Inputs, 4 x Spare. (red-red-black-brown-brown)
- 20 x 6k8 End-of-line resistors. 16 x Zone Inputs, 4 x Spare. (blue-grey-black-brown-brown)
- Spiral bound User Manual.
- User’s Quick Reference Card. (4 page booklet)
- Installation Manual. (This document)
In countries where the Mains input cable is not pre-fitted, the following parts are also supplied:
- 3 x Conductive Sleeves for AC Power cable termination.
- 1 x Plastic Cable grommet.
- Sufficient mounting screws to assemble all parts to housing.

Other manuals for Inner Range 3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inner Range 3000 and is the answer not in the manual?

Inner Range 3000 Specifications

Power IconPower
power supply input voltage11V to 14V DC
standby current consumption25mA
logged on current consumption35 to 40mA
lock relay active current consumption60mA
all auxiliaries active current consumption105mA
lock relay contacts voltage30V DC maximum
lock relay contacts current750mA maximum
fuse protection500mA Reader Power Fuse
Operating Environment IconOperating Environment
module pcb temperature range0º to 40º Celsius
module pcb humidity range15% to 85% Relative humidity (non-condensing)
keypad temperature range-20º to 70º Celsius
keypad moisture and dust ratingIP68
Weight and Dimensions IconWeight and Dimensions
pcb length96mm
pcb width96mm
keypad height130mm
keypad width81mm
keypad depth21mm
distance between mounting hole centres82.2mm
mounting hole diameter4.15mm