EasyManua.ls Logo

Inovance AC700 Series - Environmental Specifications

Inovance AC700 Series
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Specifications
-11-
2.2 Environmental Specifications
Item
Working
Transportation
Storage
Environment
parameters
(IEC60721-3)
Class
IE33 IE22 IE12
Temperature
–5°C to +55°C –40°C to +70°C –25℃ to +70°C
Humidity 10% to 95%, no-condensation
Vibration
Frequency 5 Hz to 150 Hz
2M2 1M2
Displacement
3.5 mm (direct
installation) (< 9 Hz)
Acceleration
1 g (direct
installation) (> 9 Hz)
Direction 3 axial directions
Impact (collision) 15 g, 11 ms, half sine
wave, 3 axial
directions
Altitude/air pressure
0 m to 2000 m
0 m to 3000 m (> 70 kPa)
2.3 EMC Specifications
The following table provides EMC specifications of the AC700 series controller.
No. Item
Standard
Description
1
Conducted emission
Power terminals
IEC61131-2:2017
IEC 61000-6-4:2018
Class A
2
Radiated emission
Controller
IEC61131-2:2017
IEC 61000-6-4:2018
Class A
3 ESD
IEC61131-2:2017
IEC 61000-4-2:2008
±6 kV (contact discharge)
±8 kV (air discharge)
4
Radiated susceptibility (RS)
IEC61131-2:2017
IEC 61000-4-3:2006
+A1:2007+A2:2010
80 MHz to 1000 MHz 10 V/m,
1.4 GHz to 6 GHz 10 V/m
5
EFT/Burst,
DC power terminal
IEC61131-2:2017
IEC 61000-4-4:2012
±2 kV, direct injection
(5/50 ns, 5/100 kHz)
6
EFT/Burst,
Communication and signal
ports
IEC61131-2:2017
IEC 61000-4-4:2012
±2 kV, capacitive coupling
clamp
(5/50 ns, 5/100 kHz)
7
Conducted susceptibility (CS)
DC power terminal
IEC61131-2:2017
IEC 61000-4-6:2013
0.15 MHz to 230 MHz,
(1 kHz, AM 80%)
10 V, CDN
8
Conducted susceptibility (CS)
Communication and signal
ports
IEC61131-2:2017
IEC 61000-4-6:2013
0.15 MHz to 230 MHz,
(1 kHz, AM 80%)
10 V, electromagnetic clamp
9
Surge
DC power terminal
IEC61131-2:2017
IEC 61000-4-5:2014+
A1:2017
±1 kV (line to ground)
±0.5 kV (line to line)