Wiring
-33-
Cable with the cord end terminal
Preparation procedure:
1. Strip the insulation layer to expose 6 mm of the conductor. Pass the cable through a cable marking
sleeve.
2. Insert the exposed conductor into the terminal, and then crimp the terminal with a crimping tool
recommended by the terminal manufacturer.
3. Insert the terminal into the terminal block and fix it with a screwdriver to a tightening torque not
larger than 0.45 N.m.
For the 2*11-pin dual-row connector used for I/O communication, the terminal requirements are as
follows:
Category
Terminal Size Length of Metal Part
(L2)
Stripping Length
Cord end with sheath (max.
conductor OD: 2.6 mm)
1.00 mm² [H1.0/18D]
12 mm 15 mm
0.75 mm² [H0.75/18D]
12 mm 14 mm
0.50 mm² [H0.5/16D]
10 mm 12 mm
0.34 mm² [H0.34/12D]
8 mm 10 mm
0.25 mm² [H0.25/12D]
8 mm 10 mm
0.14 mm² [H0.14/12D]
8 mm 10 mm
Naked end
1.50 mm² [H1.5/10D]
10 mm 10 mm