EasyManua.ls Logo

Inovance AM600 Series - Page 104

Inovance AM600 Series
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-103-
Introduction
Note 1: For AM600-4TC
,
the L4+/L4-~L7+/L7- channels are reserved;
Note 2: For AM600-8TC
,
the L7 sampling channel is used for compatibility which supports normal
thermocouple sampling and external cold-side compensation. When the cold side of the thermocouple
is far from the module
,
and the temperature di󶍽erence is large
,
use the channel for external cold-side
compensation if the requirement on temperature accuracy is high. In this case
,
you need to connect the
PT100 thermal resistor for compensation
,
and only CH0 to CH6 of the module are used for TC sampling.
External wiring
TC
24 V
COM
FG
Filter
DC/DC
converter
Filter
Filter
L0+
L0-
L7+
L7-
AGND
AGND
AGND
AGND
5 V
5 V
5 V
24 V
external DC
power
TC
Filter
L6+
L6-
AGND
5 V
TC sampling
2
2
5
3
1
For external cold-side
compensation
PT
4
TC
2
1
TC sampling
TC sampling
For internal cold-side
compensation
1
1
2
Figure 5-47 AM600-8TC module wiring
NOTE
*1 Use shielded compensation wires.
*2 If there is distance between cold-side compensation and thermocouple end
,
and no
compensation wire is used
,
the temperature measurement is abnormal.
*3 Channel L7 can use PT100 thermal resistors for cold-side compensation
,
and you need to
use the software to enable this channel.
*4 If the module uses internal cold-side compensation
,
the L7 channel can be used for normal
thermocouple sampling
,
and the wiring is as shown in L0 - L6 in the preceding 󶍾gure; if the
module uses external cold-side compensation
,
you need to connect the PT100 thermal
resistor to the L7 channel
,
and the wiring is as shown in L7 in the preceding 󶍾gure.
*5 The module must be mounted on a well-grounded metal bracket
,
and ensure that the
metal spring plate at the bottom of the module is in good contact with the bracket.