EasyManua.ls Logo

Inovance AM600 Series - Specifications of the Power Module

Inovance AM600 Series
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-30-
Introduction
3.3 Speci󶍾cations of the Power Module
1 Basic speci󶍾cations
Item Name Rated Value Test Conditions Remarks
Insulation
resistance
Primary side -
SELV
≥ 2 x 106 Ω
Ambient temperature: 25±5℃
,
relative humidity: < 90% (without
condensation)
,
test voltage: 500 V DC
Comply with LVD
directives.
Primary side - PE ≥ 2 x 106 Ω
Voltage
resistance
Enhanced
insulation
Primary side - SELV: Capable of withstanding 3250 VDC (or
2300 VAC) for one minute
No arcing or
breakdown with
the leakage current
lower than 10 mA.
Basic insulation
Primary side - PE (or grounding housing): Capable of
withstanding 1900 VDC (or 1350 VAC) for one minute
Pulse
Enhanced
insulation
Primary side - SELV: Capable of withstanding 4250 V
pulses
No arcing or
breakdown
Basic insulation
Primary side - PE (or grounding housing): Capable of
withstanding 2500 V pulses
Rated input
voltage range
AC input 100 VAC to 240 VAC (-15% to +10%) -
Input frequency 50/60 Hz (-5% to +5%) -
Rated input current Up to 1.0 A -
Output voltage 24 VDC ± 5% -
Rated output current 2 A -
E󶎀ciency Above 70% -
IP class IP20 -
Overvoltage class
Pluggable or 󶍾xed devices that obtain power from indoor
sockets
-
Overcurrent protection device 2 A fuse Internal fuse
2 Module interface description
"$JOQVU
-
/
 7"$
*/165
065165
 7%$"
108&3
"$HSPVOE
)PVTJOHHSPVOE
%$PVUQVU
Figure 3-6 Interfaces of the power module
The power module has two terminals. the AC input terminal and the DC output terminal. The AC input
terminal must meet the following requirements:

Table of Contents